Enfinium
← Back to Ferrybridge 1

Bag Cleaning Cycle Frequency (/ h)

Ferrybridge 1 · FGT / Emissions / CEMS

60.5/ h44.0/ h27.5/ h11.0/ h-5.5/ hT-24T-23T-22T-21T-20T-19T-18T-17T-16T-15T-14T-13T-12T-11T-10T-9T-8T-7T-6T-5T-4T-3T-2T-1Trending down -0.4/ h over period
What this shows

Recent values for Bag Cleaning Cycle Frequency. Green band is the agreed operating window (30-45 / h); amber is the early-warning band before action is required. Source: auto.

Why it's trending this way

Currently in band at 38 / h. Schedule pulse-clean optimisation on bag filters, ΔP creeping.

Historical data
PeriodValueTargetDeltaStatus
T-2439.2/ h0.0/ h+39.2/ hOn / above target
T-2337.8/ h0.0/ h+37.8/ hOn / above target
T-2237.6/ h0.0/ h+37.6/ hOn / above target
T-2136.1/ h0.0/ h+36.1/ hOn / above target
T-2036.9/ h0.0/ h+36.9/ hOn / above target
T-1935.5/ h0.0/ h+35.5/ hOn / above target
T-1835.8/ h0.0/ h+35.8/ hOn / above target
T-1735.9/ h0.0/ h+35.9/ hOn / above target
T-1636.7/ h0.0/ h+36.7/ hOn / above target
T-1538.4/ h0.0/ h+38.4/ hOn / above target
T-1437.9/ h0.0/ h+37.9/ hOn / above target
T-1338.9/ h0.0/ h+38.9/ hOn / above target
T-1239.4/ h0.0/ h+39.4/ hOn / above target
T-1139.5/ h0.0/ h+39.5/ hOn / above target
T-1039.8/ h0.0/ h+39.8/ hOn / above target
T-939.5/ h0.0/ h+39.5/ hOn / above target
T-839.1/ h0.0/ h+39.1/ hOn / above target
T-737.8/ h0.0/ h+37.8/ hOn / above target
T-636.9/ h0.0/ h+36.9/ hOn / above target
T-536.1/ h0.0/ h+36.1/ hOn / above target
T-435.8/ h0.0/ h+35.8/ hOn / above target
T-336.6/ h0.0/ h+36.6/ hOn / above target
T-235.5/ h0.0/ h+35.5/ hOn / above target
T-137.0/ h0.0/ h+37.0/ hOn / above target