Enfinium
← Back to Ferrybridge 1

Bag Chamber Flue Gas Outlet Temps (°C)

Ferrybridge 1 · FGT / Emissions / CEMS

198.0°C144.0°C90.0°C36.0°C-18.0°CT-24T-23T-22T-21T-20T-19T-18T-17T-16T-15T-14T-13T-12T-11T-10T-9T-8T-7T-6T-5T-4T-3T-2T-1Trending up +2.0°C over period
What this shows

Recent values for Bag Chamber Flue Gas Outlet Temps. Green band is the agreed operating window (140-170 °C); amber is the early-warning band before action is required. Source: auto.

Why it's trending this way

Currently in band at 158 °C. Schedule pulse-clean optimisation on bag filters, ΔP creeping.

Historical data
PeriodValueTargetDeltaStatus
T-24150.8°C0.0°C+150.8°COn / above target
T-23151.9°C0.0°C+151.9°COn / above target
T-22149.9°C0.0°C+149.9°COn / above target
T-21154.0°C0.0°C+154.0°COn / above target
T-20159.4°C0.0°C+159.4°COn / above target
T-19159.5°C0.0°C+159.5°COn / above target
T-18162.8°C0.0°C+162.8°COn / above target
T-17167.4°C0.0°C+167.4°COn / above target
T-16168.3°C0.0°C+168.3°COn / above target
T-15167.9°C0.0°C+167.9°COn / above target
T-14162.4°C0.0°C+162.4°COn / above target
T-13159.9°C0.0°C+159.9°COn / above target
T-12157.2°C0.0°C+157.2°COn / above target
T-11153.9°C0.0°C+153.9°COn / above target
T-10154.1°C0.0°C+154.1°COn / above target
T-9148.1°C0.0°C+148.1°COn / above target
T-8150.0°C0.0°C+150.0°COn / above target
T-7153.3°C0.0°C+153.3°COn / above target
T-6152.9°C0.0°C+152.9°COn / above target
T-5154.1°C0.0°C+154.1°COn / above target
T-4156.7°C0.0°C+156.7°COn / above target
T-3160.4°C0.0°C+160.4°COn / above target
T-2162.0°C0.0°C+162.0°COn / above target
T-1168.3°C0.0°C+168.3°COn / above target