FGT / Emissions / CEMS
Skelton Grange · Owner Environmental Lead
Headline indicator
312kg/h · Lime Consumption
Green band 260-340 · Amber 240-380 · Red beyond.
Recommended action
Schedule pulse-clean optimisation on bag filters, ΔP creeping.
Owner: Environmental Lead
Open actions: 1
9 sub-KPIs · automated 8 · manual 0 · mixed 1 · needs definition 0
Data sourceAutomatedManualMixedNeeds definition
Sub-KPIs · tap any tile for full chart, history & interpretation
Lime Consumption
Automated312kg/h
Green 260-340 · Amber 240-380
Carbon Consumption
Automated42kg/h
Green 35-50 · Amber 30-55
Residue Recirculation (F1/F2)
Automated0.78ratio
Green 0.7-0.9 · Amber 0.6-1
Baghouse ΔP
Automated1.6kPa
Green 1-1.8 · Amber 1.8-2.2
Bag Cleaning Cycle Frequency
Automated38/ h
Green 30-45 · Amber 25-55
Air Ingress / O₂ Diff
Automated0.6%
Green 0-1 · Amber 1-1.5
Bag Chamber Flue Gas Outlet Temps
Automated158°C
Green 140-170 · Amber 130-180
Silo / Transport System Status
Mixed1OK
Green 1-1 · Amber 0-1
CEMS Status
Automated1OK
Green 1-1 · Amber 0-1
Operating detail
NOx
142mg/Nm³
SO₂
18mg/Nm³
HCl
6mg/Nm³
Bag-filter ΔP trend
+0.2 in 14d