Enfinium
← Back to Kelvin Lane

Bag Chamber Flue Gas Outlet Temps (°C)

Kelvin Lane · FGT / Emissions / CEMS

198.0°C144.0°C90.0°C36.0°C-18.0°CT-24T-23T-22T-21T-20T-19T-18T-17T-16T-15T-14T-13T-12T-11T-10T-9T-8T-7T-6T-5T-4T-3T-2T-1Trending up +1.4°C over period
What this shows

Recent values for Bag Chamber Flue Gas Outlet Temps. Green band is the agreed operating window (140-170 °C); amber is the early-warning band before action is required. Source: auto.

Why it's trending this way

Currently in band at 158 °C. Schedule pulse-clean optimisation on bag filters, ΔP creeping.

Historical data
PeriodValueTargetDeltaStatus
T-24153.1°C0.0°C+153.1°COn / above target
T-23154.8°C0.0°C+154.8°COn / above target
T-22159.8°C0.0°C+159.8°COn / above target
T-21158.5°C0.0°C+158.5°COn / above target
T-20163.6°C0.0°C+163.6°COn / above target
T-19168.2°C0.0°C+168.2°COn / above target
T-18164.3°C0.0°C+164.3°COn / above target
T-17164.3°C0.0°C+164.3°COn / above target
T-16165.2°C0.0°C+165.2°COn / above target
T-15160.5°C0.0°C+160.5°COn / above target
T-14157.1°C0.0°C+157.1°COn / above target
T-13155.4°C0.0°C+155.4°COn / above target
T-12150.4°C0.0°C+150.4°COn / above target
T-11148.4°C0.0°C+148.4°COn / above target
T-10152.7°C0.0°C+152.7°COn / above target
T-9153.5°C0.0°C+153.5°COn / above target
T-8150.1°C0.0°C+150.1°COn / above target
T-7154.2°C0.0°C+154.2°COn / above target
T-6156.6°C0.0°C+156.6°COn / above target
T-5161.5°C0.0°C+161.5°COn / above target
T-4166.4°C0.0°C+166.4°COn / above target
T-3163.5°C0.0°C+163.5°COn / above target
T-2167.8°C0.0°C+167.8°COn / above target
T-1163.5°C0.0°C+163.5°COn / above target