Steam/Feed Diff (Tube Leak) (t/h)
Parc Adfer · Boiler Pressure Parts
What this shows
Recent values for Steam/Feed Diff (Tube Leak). Green band is the agreed operating window (0-1 t/h); amber is the early-warning band before action is required. Source: auto.
Why it's trending this way
Currently in band at 0.4 t/h. Confirm next-outage corrosion zone temperature band; bring forward UT inspection.
Historical data
| Period | Value | Target | Delta | Status |
|---|---|---|---|---|
| T-24 | 0.5t/h | 0.0t/h | +0.5t/h | On / above target |
| T-23 | 0.6t/h | 0.0t/h | +0.6t/h | On / above target |
| T-22 | 0.6t/h | 0.0t/h | +0.6t/h | On / above target |
| T-21 | 0.6t/h | 0.0t/h | +0.6t/h | On / above target |
| T-20 | 0.5t/h | 0.0t/h | +0.5t/h | On / above target |
| T-19 | 0.5t/h | 0.0t/h | +0.5t/h | On / above target |
| T-18 | 0.4t/h | 0.0t/h | +0.4t/h | On / above target |
| T-17 | 0.4t/h | 0.0t/h | +0.4t/h | On / above target |
| T-16 | 0.3t/h | 0.0t/h | +0.3t/h | On / above target |
| T-15 | 0.2t/h | 0.0t/h | +0.2t/h | On / above target |
| T-14 | 0.3t/h | 0.0t/h | +0.3t/h | On / above target |
| T-13 | 0.2t/h | 0.0t/h | +0.2t/h | On / above target |
| T-12 | 0.3t/h | 0.0t/h | +0.3t/h | On / above target |
| T-11 | 0.4t/h | 0.0t/h | +0.4t/h | On / above target |
| T-10 | 0.4t/h | 0.0t/h | +0.4t/h | On / above target |
| T-9 | 0.5t/h | 0.0t/h | +0.5t/h | On / above target |
| T-8 | 0.5t/h | 0.0t/h | +0.5t/h | On / above target |
| T-7 | 0.7t/h | 0.0t/h | +0.7t/h | On / above target |
| T-6 | 0.6t/h | 0.0t/h | +0.6t/h | On / above target |
| T-5 | 0.5t/h | 0.0t/h | +0.5t/h | On / above target |
| T-4 | 0.5t/h | 0.0t/h | +0.5t/h | On / above target |
| T-3 | 0.4t/h | 0.0t/h | +0.4t/h | On / above target |
| T-2 | 0.3t/h | 0.0t/h | +0.3t/h | On / above target |
| T-1 | 0.3t/h | 0.0t/h | +0.3t/h | On / above target |