Enfinium
← Back to Skelton Grange

Fouling Diffs (kPa)

Skelton Grange · Boiler Flue Gas Path / Combustion

2.2kPa1.6kPa1.0kPa0.4kPa-0.2kPaT-24T-23T-22T-21T-20T-19T-18T-17T-16T-15T-14T-13T-12T-11T-10T-9T-8T-7T-6T-5T-4T-3T-2T-1Flat trend
What this shows

Recent values for Fouling Diffs. Green band is the agreed operating window (0-1.6 kPa); amber is the early-warning band before action is required. Source: auto.

Why it's trending this way

Currently in band at 1.42 kPa. Schedule combustion-control re-tune; grate speed trend creeping.

Historical data
PeriodValueTargetDeltaStatus
T-241.4kPa0.0kPa+1.4kPaOn / above target
T-231.4kPa0.0kPa+1.4kPaOn / above target
T-221.3kPa0.0kPa+1.3kPaOn / above target
T-211.2kPa0.0kPa+1.2kPaOn / above target
T-201.1kPa0.0kPa+1.1kPaOn / above target
T-191.1kPa0.0kPa+1.1kPaOn / above target
T-181.2kPa0.0kPa+1.2kPaOn / above target
T-171.3kPa0.0kPa+1.3kPaOn / above target
T-161.4kPa0.0kPa+1.4kPaOn / above target
T-151.5kPa0.0kPa+1.5kPaOn / above target
T-141.6kPa0.0kPa+1.6kPaOn / above target
T-131.6kPa0.0kPa+1.6kPaOn / above target
T-121.7kPa0.0kPa+1.7kPaOn / above target
T-111.7kPa0.0kPa+1.7kPaOn / above target
T-101.6kPa0.0kPa+1.6kPaOn / above target
T-91.5kPa0.0kPa+1.5kPaOn / above target
T-81.4kPa0.0kPa+1.4kPaOn / above target
T-71.3kPa0.0kPa+1.3kPaOn / above target
T-61.2kPa0.0kPa+1.2kPaOn / above target
T-51.2kPa0.0kPa+1.2kPaOn / above target
T-41.2kPa0.0kPa+1.2kPaOn / above target
T-31.1kPa0.0kPa+1.1kPaOn / above target
T-21.3kPa0.0kPa+1.3kPaOn / above target
T-11.3kPa0.0kPa+1.3kPaOn / above target